Reviewed by Matt Servini, founder of The Craft Distilling Business, a UK distillery design-and-build specialist.
ATEX certification for a distillery applies only to equipment placed inside a classified hazardous zone, not to the whole installation. Under DSEAR, you assess the risk, zone the areas where flammable vapour can form, and certify only the kit that sits in those zones. Because a still can usually be designed with its electrics outside the hazard zone, most distilleries need far less certified equipment, and far less cost, than the common myth suggests.
Table of Contents
- Does Every Distillery Need ATEX Certification? The Costly Myth
- DSEAR: The Regulation That Actually Applies
- Hazardous Area Zoning Explained (Zones 0, 1 and 2)
- ATEX and UKEX: What They Are and When They Apply
- What Needs Certification and What Does Not
- How Good Still Design Keeps Electrics Out of the Zone
- Getting Zoning, Risk Assessment and SOPs Right Early
- Frequently Asked Questions

Does Every Distillery Need ATEX Certification? The Costly Myth
One of the most expensive misconceptions in craft distilling is that every piece of equipment in the building must hold ATEX certification or its UKEX equivalent. It is not true, and acting on it can add thousands of pounds to a project that did not need spending.
The reality is narrower. Certification applies to equipment that sits inside a defined hazardous zone, the small volume of space where a flammable vapour could realistically be present. It does not apply to equipment outside that zone, even when it is in the same room. Get the zoning right and the list of kit that genuinely needs certified protection is usually short.
This matters because the myth drives two costly decisions: buying certified versions of equipment that never needed them, and hiring an ATEX certified electrician to install electrics that were never going to sit in the zone. Both are avoidable with the right design from the outset.
DSEAR: The Regulation That Actually Applies
In Great Britain, the regulation that governs flammable atmospheres in a distillery is DSEAR, the Dangerous Substances and Explosive Atmospheres Regulations 2002. Ethanol vapour is a dangerous substance, so any distillery handling spirit at strength falls within its scope.
According to the Health and Safety Executive, DSEAR requires employers to assess the risk of fire and explosion from dangerous substances and to eliminate or reduce that risk so far as is reasonably practicable. It also introduced a specific legal duty to carry out a hazardous area study and document the conclusions as zones.
DSEAR is the duty that sits on you as the operator: assess, zone, and control ignition sources. ATEX and UKEX, covered below, are the product rules that say what an item of equipment must meet if it is going to be used inside one of those zones. The two work together, but they are not the same thing, and conflating them is where overspending starts.
Hazardous Area Zoning Explained (Zones 0, 1 and 2)
Zoning is the step that decides everything else. Under DSEAR, areas where a flammable gas or vapour may form are classified into three zones based on how likely an explosive atmosphere is and how long it persists. The HSE confirms that the classification, size and location of each zone depend on that likelihood and persistence.
For gases and vapours, the zones map to equipment categories as follows.
| Zone | When a flammable atmosphere is present | Equipment category required inside the zone |
|---|---|---|
| Zone 0 | Continuously, or for long periods, or frequently | Category 1G (very high protection) |
| Zone 1 | Likely to occur in normal operation occasionally | Category 2G (high protection) |
| Zone 2 | Not likely in normal operation, and only briefly if it does | Category 3G (normal protection) |
In a well-designed distillery, the zone is small and tightly drawn: often the immediate space around the still’s vapour path, charging point or spirit receiver, rather than the whole room. The smaller and better-controlled the zone, the less equipment falls inside it. This is why zoning is a design decision, not a box-ticking exercise after the kit is installed.
ATEX and UKEX: What They Are and When They Apply
ATEX and UKEX describe equipment that is certified safe for use inside a hazardous zone. The names cover the same idea on either side of the Channel.
ATEX is the long-standing EU framework, carried by the CE mark and the Ex symbol. UKEX is the Great Britain equivalent introduced after Brexit, set out in the Equipment and Protective Systems Intended for Use in Potentially Explosive Atmospheres Regulations 2016 and shown by the UKCA mark alongside the Ex symbol. The technical requirements are closely aligned, and the UK government continues to accept CE-marked ATEX equipment on the GB market, so in practice you can specify either.
The post-Brexit position has been a moving target, so it is worth being precise. The 2016 Regulations created the UKEX route and the UKCA mark for Great Britain, while CE marking remained the recognised mark for the EU and Northern Ireland. The acceptance of CE-marked products in Great Britain was originally framed as time-limited, but the government has since confirmed it indefinitely for a broad set of product regulations, including equipment for potentially explosive atmospheres. In short, a distiller buying ATEX-rated kit today does not need to fear that a CE-marked Ex item will suddenly become unusable on the GB market. Whether you specify ATEX or UKEX, the underlying safety standards your equipment is built to are effectively the same, so the choice is rarely the thing that decides cost. What decides cost is how much equipment ends up needing any mark at all, which comes back to the zone.
The key point is when this applies. ATEX or UKEX certification is required for an item that will operate inside a classified zone. It is not required for equipment that sits outside every zone. A certified mark on a control panel mounted on the far wall buys you nothing if that wall was never in the zone in the first place.
What Needs Certification and What Does Not
It helps to separate the kit into what typically needs certified protection and what typically does not, given a sensibly zoned installation.
| Usually needs ATEX / UKEX equipment | Usually does not |
|---|---|
| Electrical items that must sit inside the zone | The still vessel and pot itself (no ignition source) |
| Extraction or fans drawing vapour-laden air | Control panels and electrics mounted outside the zone |
| Pumps or instruments located in the zone | Heating designed to operate from outside the zone |
| Lighting fitted within a classified area | General room lighting and sockets outside the zone |
The copper, the column and the condenser are not in themselves ignition sources, so the structure of the still is rarely the issue. The question is always about ignition sources, which in practice means electrical components, and whether they are inside or outside the zone. Move them out, and the certification requirement usually moves with them. You can see the kind of installations this thinking produces across our distillery projects.
How Good Still Design Keeps Electrics Out of the Zone
This is where bespoke design pays for itself. Rather than buy a standard still and then try to certify whatever ends up in the zone, the better approach is to design the still and its layout so the electrics never sit in the zone at all.
In practice that means siting control panels, contactors and instrumentation outside the classified area, routing power so that the only items near the vapour path are passive, and using extraction and layout to keep the zone small and well-ventilated. Done properly, this means the equipment does not need an ATEX certified electrician to install it: a competent general electrician can complete the work, which is markedly cheaper. We have applied this in some genuinely demanding settings, including airports and cruise ships, where space and safety constraints leave no margin for a sloppy zone.
Every distillery we build is bespoke for exactly this reason. Designing the hazard out, instead of certifying around it, is usually the lowest-cost route to a compliant, safe installation. Our services to help operate your distillery include this design work alongside the health and safety documentation that goes with it.
Northern Ireland
Northern Ireland follows a unique regulatory framework because of the Windsor Framework. If you are considering opening a distillery in Northern Ireland, get in touch with us and we will talk you through what applies to your site.
Getting Zoning, Risk Assessment and SOPs Right Early
The cheapest time to get this right is before anything is installed. A DSEAR risk assessment and a documented hazardous area classification should come first, because they define the zone, and the zone defines what, if anything, needs certifying.
From there, every installation needs Standard Operating Procedures and risk assessments written for the specific site: how the still is charged, how vapour is managed, how the zone is maintained, and what happens in an upset. These are not generic templates. They reflect the actual layout, ventilation and process, and they are also what a local authority or insurer will expect to see. If you are weighing up suppliers, it is worth asking each one how they handle DSEAR zoning and certification up front, rather than treating it as an afterthought, which is exactly the approach we take on every bespoke distillery build.
Get the assessment, the zoning and the documentation right at the design stage and the rest of the project, certification, installation and sign-off, runs far more smoothly and at lower cost. We provide this documentation as part of a turnkey build, and you can browse common queries on our frequently asked questions hub.
What to Ask Before You Buy
If you are speaking to equipment suppliers, a few questions tell you how seriously they have thought about this. Has the hazardous zone been assessed for this specific setup, or is certification applied as a blanket default? Which components, specifically, sit inside the zone and need certification, and which do not? Who is doing the installation, and do they hold the relevant Ex qualification if certified equipment is involved? A supplier who answers these clearly, rather than defaulting to the idea that everything needs certification because it is safer, has engineered the risk rather than priced around it.
Frequently Asked Questions
Does all distillery equipment need ATEX certification?
No. Only equipment located inside a classified hazardous zone needs ATEX or UKEX certified protection. A still can usually be designed so its electrical components sit outside the hazard zone, which means most of the kit needs no certification at all.
What is the difference between ATEX and UKEX?
ATEX is the EU framework for equipment used in explosive atmospheres. UKEX is the Great Britain equivalent introduced after Brexit under the 2016 Regulations, shown by the UKCA and Ex marks. The technical requirements are closely aligned, and CE-marked ATEX equipment is still accepted on the GB market.
What is DSEAR and does it apply to a distillery?
DSEAR is the Dangerous Substances and Explosive Atmospheres Regulations 2002. It applies to any workplace where flammable vapours can form, which includes distilleries handling ethanol. It requires a risk assessment, hazardous area zoning and control of ignition sources.
Do I need an ATEX certified electrician for my distillery?
Only if electrical equipment has to sit inside a hazardous zone. Where the still is designed to keep electrics outside the zone, a competent general electrician can complete the work and no ATEX certified specialist is required, which is considerably cheaper.
How do hazardous zones work in a distillery?
Under DSEAR, areas where a flammable atmosphere may form are classified into Zone 0, Zone 1 or Zone 2 for gases and vapours, based on how likely and how persistent that atmosphere is. The zone determines what, if any, certified equipment is needed in that space.
References
Sources used in this guide, for readers who want the underlying regulation and research.
- Directive 2014/34/EU on equipment and protective systems intended for use in potentially explosive atmospheres (ATEX). https://eur-lex.europa.eu/legal-content/EN/TXT/?uri=CELEX:32014L0034
- Directive 1999/92/EC (ATEX 137) on minimum requirements for improving the safety and health of workers at risk from explosive atmospheres. https://eur-lex.europa.eu/eli/dir/1999/92/oj
- The Equipment and Protective Systems Intended for use in Potentially Explosive Atmospheres Regulations 2016 (SI 2016 No. 1107). https://www.legislation.gov.uk/uksi/2016/1107/contents/made
- HSE. Dangerous substances and explosive atmospheres. DSEAR Approved Code of Practice L138. https://www.hse.gov.uk/pubns/books/l138.htm
- BS EN 60079-10-1:2021. Explosive atmospheres. Classification of areas. Explosive gas atmospheres. https://knowledge.bsigroup.com/products/explosive-atmospheres-classification-of-areas-explosive-gas-atmospheres